Range of Product | TeSys Deca |
---|---|
Product or Component Type | Contactor |
Device short name | LC1D |
contactor application | Motor control Resistive load |
Utilisation category | AC-1 AC-4 AC-3 AC-3e |
poles description | 3P |
[Ue] rated operational voltage | Power circuit <= 690 V AC 25…400 Hz Power circuit <= 300 V DC |
[Ie] rated operational current | 18 A (at <140.0000000000 °F (60 °C)) at <= 440 V AC AC-3 for power circuit 32 A (at <140.0000000000 °F (60 °C)) at <= 440 V AC AC-1 for power circuit 18 A (at <140.0000000000 °F (60 °C)) at <= 440 V AC AC-3e for power circuit |
[Uc] control circuit voltage | 110 V AC 50/60 Hz |
Motor power kW | 4 kW at 220…230 V AC 50/60 Hz (AC-3) 7.5 kW at 380…400 V AC 50/60 Hz (AC-3) 9 kW at 415…440 V AC 50/60 Hz (AC-3) 10 kW at 500 V AC 50/60 Hz (AC-3) 10 kW at 660…690 V AC 50/60 Hz (AC-3) 4 kW at 400 V AC 50/60 Hz (AC-4) 4 kW at 220…230 V AC 50/60 Hz (AC-3e) 7.5 kW at 380…400 V AC 50/60 Hz (AC-3e) 9 kW at 415…440 V AC 50/60 Hz (AC-3e) 10 kW at 500 V AC 50/60 Hz (AC-3e) 10 kW at 660…690 V AC 50/60 Hz (AC-3e) |
---|---|
Maximum Horse Power Rating | 1 hp at 115 V AC 50/60 Hz for 1 phase motors 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors 5 hp at 200/208 V AC 50/60 Hz for 3 phase motors 5 hp at 230/240 V AC 50/60 Hz for 3 phase motors 10 hp at 460/480 V AC 50/60 Hz for 3 phase motors 15 hp at 575/600 V AC 50/60 Hz for 3 phase motors |
Compatibility code | LC1D |
Pole contact composition | 3 NO |
Protective cover | With |
[Ith] conventional free air thermal current | 10 A (at 140.0000000000 °F (60 °C)) for signalling circuit 32 A (at 140.0000000000 °F (60 °C)) for power circuit |
Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 300 A at 440 V for power circuit conforming to IEC 60947 |
Rated breaking capacity | 300 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current | 145 A 104.0000000000 °F (40 °C) – 10 s for power circuit 240 A 104.0000000000 °F (40 °C) – 1 s for power circuit 40 A 104.0000000000 °F (40 °C) – 10 min for power circuit 84 A 104.0000000000 °F (40 °C) – 1 min for power circuit 100 A – 1 s for signalling circuit 120 A – 500 ms for signalling circuit 140 A – 100 ms for signalling circuit |
Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1 50 A gG at <= 690 V coordination type 1 for power circuit 35 A gG at <= 690 V coordination type 2 for power circuit |
Average impedance | 2.5 mOhm – Ith 32 A 50 Hz for power circuit |
Power dissipation per pole | 2.5 W AC-1 0.8 W AC-3 0.8 W AC-3e |
[Ui] rated insulation voltage | Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL |
Overvoltage category | III |
Pollution degree | 3 |
[Uimp] rated impulse withstand voltage | 6 kV IEC 60947 |
Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
Mechanical durability | 15 Mcycles |
Electrical durability | 1.65 Mcycles 18 A AC-3 <= 440 V 1 Mcycles 32 A AC-1 <= 440 V 1.65 Mcycles 18 A AC-3e <= 440 V |
Control circuit type | AC 50/60 Hz standard |
Coil technology | Without built-in suppressor module |
Control circuit voltage limits | 0.3…0.6 Uc -40.0000000000…158.0000000000 °F (-40…70 °C) drop-out AC 50/60 Hz 0.8…1.1 Uc -40.0000000000…140.0000000000 °F (-40…60 °C) operational AC 50 Hz 0.85…1.1 Uc -40.0000000000…140.0000000000 °F (-40…60 °C) operational AC 60 Hz 1…1.1 Uc 140.0000000000…158.0000000000 °F (60…70 °C) operational AC 50/60 Hz |
Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 68.0000000000 °F (20 °C)) 70 VA 50 Hz cos phi 0.75 (at 68.0000000000 °F (20 °C)) |
Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 68.0000000000 °F (20 °C)) 7 VA 50 Hz cos phi 0.3 (at 68.0000000000 °F (20 °C)) |
Heat dissipation | 2…3 W at 50/60 Hz |
Operating time | 12…22 ms closing 4…19 ms opening |
Maximum operating rate | 3600 cyc/h 140.0000000000 °F (60 °C) |
Connections – terminals | Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) – cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) – cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) – cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) – cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) – cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) – cable stiffness: solid without cable end Power circuit: screw clamp terminals 1 0.002…0.009 in² (1.5…6 mm²) – cable stiffness: flexible without cable end Power circuit: screw clamp terminals 2 0.002…0.009 in² (1.5…6 mm²) – cable stiffness: flexible without cable end Power circuit: screw clamp terminals 1 0.002…0.009 in² (1…6 mm²) – cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) – cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 0.002…0.009 in² (1.5…6 mm²) – cable stiffness: solid without cable end Power circuit: screw clamp terminals 2 0.002…0.009 in² (1.5…6 mm²) – cable stiffness: solid without cable end |
Tightening torque | Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2 Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2 |
Auxiliary contact composition | 1 NO + 1 NC |
Auxiliary contacts type | Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1 |
Signalling circuit frequency | 25…400 Hz |
Minimum switching voltage | 17 V for signalling circuit |
Minimum switching current | 5 mA for signalling circuit |
Insulation resistance | > 10 MOhm for signalling circuit |
Non-overlap time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
Mounting Support | Plate Rail |
Standards | CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 IEC 60335-1 |
---|---|
Product Certifications | GL BV DNV LROS (Lloyds register of shipping) RINA UL CCC CSA GOST UKCA CB |
IP degree of protection | IP20 front face IEC 60529 |
Protective treatment | THIEC 60068-2-30 |
Climatic withstand | IACS E10 exposure to damp heat IEC 60947-1 Annex Q category D exposure to damp heat |
Permissible ambient air temperature around the device | -40.0000000000…140.0000000000 °F (-40…60 °C) 140.0000000000…158.0000000000 °F (60…70 °C) with derating |
Operating altitude | 0…9842.52 ft (0…3000 m) |
Fire resistance | 1562.0000000000 °F (850 °C) IEC 60695-2-1 |
Flame retardance | V1 conforming to UL 94 |
Mechanical robustness | Vibrations contactor open 2 Gn, 5…300 Hz) Vibrations contactor closed 4 Gn, 5…300 Hz) Shocks contactor open 10 Gn for 11 ms) Shocks contactor closed 15 Gn for 11 ms) |
Height | 3.03 in (77 mm) |
Width | 1.8 in (45 mm) |
Depth | 3.4 in (86 mm) |
Net Weight | 0.73 lb(US) (0.33 kg) |
Category | US10I1222354 |
---|---|
Discount Schedule | 0I12 |
GTIN | 3389110349450 |
Returnability | Yes |
Country of origin | MX |
دیدگاهها
هیچ دیدگاهی برای این محصول نوشته نشده است.